Preface:
Since 1990, and particularly since 1995, China's paper industry has experienced continuous growth in effective production capacity. By the end of 2002, there were over 4,000 paper mills in China, including more than 2,600 of significant scale. The total output in 2002 reached 37.8 million tons. In the following 1-2 years, nearly 10 million tons of new production capacity were added. Currently, over 80% of new paper machine drive systems utilize inverter-controlled drives.

Inverters applied in paper machine drives must currently possess the following characteristics:
(1) Wide speed regulation range, with efficiency above 90% across the entire speed range;
(2) Power factor higher than 0.9;
(3) Total harmonic distortion of input current less than 3%;
(4) Use of reliable, mature standard components like IGBTs;
(5) Ability to reduce output harmonic content and effectively lower dv/dt noise and torque pulsation.

I. Background of Inverter Application in Paper Machines.
The sectional drive equipment of paper machines in China previously used SCR DC speed control systems. Issues like slip rings and carbon brushes led to low reliability and precision, resulting in outdated paper machine mechanics with speeds typically around 200 m/min, making it difficult to compete with foreign high-speed paper machines reaching 1000 m/min. Papermaking is a continuous production process, making the continuous and orderly control of the production line a bottleneck restricting paper quality and output. While DC speed control systems played a significant role in the history of paper machine development, DC motors suffer from difficulties in maintenance and poor resistance to environmental factors, mainly manifested as follows:
(1) Severe commutator wear and faults like burnt commutators leading to long downtime;
(2) Numerous difficulties and high requirements in DC motor maintenance, resulting in high repair costs;
(3) Tachogenerators prone to wear, causing low precision in the drive system;
(4) Complex DC speed control systems, difficult to debug, often making it hard for average technicians to fine-tune machine operating speeds.
AC variable frequency speed control technology, with its excellent speed regulation performance and significant energy-saving benefits, is widely applicable in China's economy and is considered the most promising AC speed control method. It not only possesses the superior speed regulation performance of DC motors but is thus gradually being widely adopted. The application of inverters in the sectional drives of future paper machines has become an inevitable trend.

The application of inverters in paper machine drives yields very good results, such as improving paper quality from a process perspective, increasing production capacity, reducing energy consumption, and extending shutdown maintenance cycles.

Taking a Fourdrinier paper machine as an example, it has two main sections: the dryer section (dry end) and the wire section (wet end). According to process requirements, the papermaking speed ranges from 20–100 m/min, with basis weights of 9–30 g/m². Generally, the drive precision requirement for paper machines is 1–3‰. Due to the wide speed variation range and a minimum basis weight of 9 g/m², even higher drive precision is required. Therefore, a closed-loop control system is chosen for the paper machine drive.

II. Analysis of Energy-saving Benefits
Based on the energy consumption comparison of a paper machine before and after retrofitting at a factory, the data is as follows:
DC Control Power Consumption: Speed at 90 m/min: P90 = 74A × 180V + 3 × 220 = 13980W = 13.98 kW (DC drive)
Based on 300 production days per year: Total machine power consumption = 300 × 24 × 13.98 = 100,656 (kWh)
Inverter Control Power Consumption: Speed at 90 m/min: P90 = 1.732 × 16A × 380V = 10530W = 10.53 (kW) (Inverter drive)
Total machine power consumption = 300 × 24 × 10.53 = 75,816 (kWh)
Annual electricity saved = 100,656 – 75,816 = 24,840 (kWh)
From this, the actual energy saving after applying the inverter can be derived as: 25%

III. Analysis of Process Benefits
(1) Increased paper machine operational rate: over 27% (derived from monthly average output, excluding other factors). This can increase production value.
(2) Improved product yield rate: 1.6%
In summary, adopting the inverter improves the operational performance of the paper machine, further enhancing economic efficiency.

IV. Application of Inverters in Paper Machine Auxiliary Equipment
Auxiliary facilities for paper machines include the following systems: stock supply system, white water system, vacuum system, compressed air system, chemical preparation and delivery system, water supply system, steam system, etc. To ensure continuous and balanced operation of the paper machine, the capacity of its auxiliary facilities generally needs to exceed the maximum production capacity of the paper machine by 15%-30%, which results in significant energy loss.

4.1 Inverter Application in the Stock Supply System
The stock supply system must meet the following conditions:
(1) Stable delivery of stock to the paper machine, with error not exceeding ±5%;
(2) Stable and uniform stock proportioning and consistency;
(3) Reserve a certain amount of stock to allow adjustment of supply capacity to adapt to changes in paper machine speed and grade;
(4) Purify and clean the stock;
(5) Handle broke from various sections of the paper machine.
Typically, the stock supply system consists of stock pumps and fan pumps in the piping, and purification equipment like pressure screens and cleaners. To achieve the above five goals, the most important step is to change stock pumps and fan pumps from full-speed operation to variable speed operation via inverters, ultimately meeting the requirements of automated stock supply.

Taking the fan pump as an example to illustrate the speed control process with an inverter: This inverter control is suitable for a dual closed-loop speed control system, with the outer loop for speed and the inner loop for current or torque. The speed setpoint for the fan pump comes from two sources: one is derived from changes in the stock-to-wire speed ratio, and the other is from the headbox pressure controller. The former is the primary adjustment, the latter is fine-tuning. The stock-to-wire speed ratio of a paper machine is essentially constant. Therefore, once the wire speed changes, the fan pump speed follows. To improve the precision of the speed regulator and reflect the actual process in the headbox, it's common to take the output of the headbox pressure PID controller, varying by ±5%, as an additional speed setpoint for the fan pump. The actual speed value is obtained from sampling the actual speed of the drive motor, which can be acquired via devices like tachogenerators or photoelectric rotary encoders. The current setpoint is taken from the output signal of the speed loop. The actual current value is taken from measurements by current transformers at the output of each drive point's AC inverter. Therefore, for variable frequency speed control of the fan pump, implementing PID control can achieve ideal energy-saving effects.

V. Inverter Application in the Compressed Air System
Compressed air is commonly used in paper machines for pneumatic loading/lifting devices in the wire and press sections, wire/felt guiding devices, air-cushioned headboxes, sheet transfer equipment, coating air knives, and various pneumatic instruments and control devices.

The main equipment in a compressed air system includes air compressors, air receivers, pressure reducing valves, air filters, moisture separators, and safety valves. Pressure required on the paper machine is typically around 5-6 BAR. In most paper mills, two or more compressors operate in parallel, maintaining constant pressure via an air receiver.

As compressors are high-power and pressure control is typically achieved by loading/unloading, motors always run at full speed. Practice shows this control method consumes enormous energy and is highly wasteful. Therefore, the trend now is to use one variable frequency drive controlling multiple line-frequency units, forming a pressure closed-loop system.

VI. Inverter Application in the Chemical Preparation and Delivery System
Large quantities of chemicals are used in deinking, pulping, coating, sizing, etc. Their usage is proportional to the speed of the paper machine's multiple drives. Therefore, variable speed AC drive systems must be used in the chemical delivery systems (e.g., pumps). Grinding equipment like ball mills, colloid mills, sand mills, and high-shear dispersers are heavily used in chemical preparation. Their main characteristics are high power, high energy consumption, and harsh operating environments. Many manufacturers have already achieved good results by using inverters on grinding equipment.

Taking a sand mill as an example: Its working principle involves feeding the material to be ground into the chamber via a feed pump. Driven by a high-speed rotating dispersion disc, the material is subjected to intense impact and grinding by the grinding media, becoming dispersed and mixed into the solvent to form a合格 coating, which then flows out through a top screen. The main motor of this equipment is 110 KW. Before using an inverter, it was common to use a jogging method multiple times (more than three) during startup to mix the coating and grinding media uniformly. For different coatings, different process speeds might be needed, but the machine could only run at full speed. Controlling the feed rate to prevent main motor overload was difficult. Energy consumption was severe. Using a 110 KW inverter effectively solves these problems: jog speed and slow run time can be easily set to ensure optimal mixing; online stepless speed regulation allows different speeds for different products; the feed rate can be controlled simply by monitoring the motor's actual running current, with overload pre-alarm and trip-free functions; energy savings generally exceed 20%; gearbox losses are reduced, avoiding impact from line-frequency starts on the gearbox; smooth starting current prevents grid impact, improving grid safety. Batch applications already exist in paper enterprises in Shandong, Heilongjiang, Hainan, and other regions.

VII. Inverter Application in the Dryer Ventilation System
In the dryer section, all moisture evaporated from the sheet, absorbed by the air, must be continuously removed from the paper machine room via forced ventilation. The effectiveness of dryer ventilation directly affects the evaporation rate of moisture from the sheet and the overall economy of the drying process. Good ventilation lowers the vapor saturation in the air, thereby reducing steam consumption in the dryer cylinders and increasing drying speed.

The necessary air volume for removing evaporated moisture from the dryer section is related to the temperature and humidity of the inlet and exhaust air, as well as the ventilation system used, climate conditions, and season. Typically, modern paper machines employ forced air circulation for high efficiency, using supply fans to deliver heated dry air (around 80°C) into the lower part of the dryer section, creating upward airflow by absorbing hot vapor between dryer cylinders, then using exhaust fans to extract the humid hot air collected in the hood to the outside (with eventual heat recovery). In high-speed paper machines, due to the increased number of dryer cylinders, multiple sets of supply and exhaust fan groups are typically used in sections. After adopting inverters, based on ventilation air volume calculation formulas, the supply air volume (supply fan speed) and exhaust air volume (exhaust fan speed) can be adjusted in real-time without using traditional damper control, further reducing energy consumption, lowering fan noise, and extending mechanical life.

VIII. Inverter Application in Water Systems
Paper machines are major water consumers, including white water systems, effluent systems, seal water systems, shower systems, fresh water systems, etc. Constant pressure water supply in the pipeline network is often required. Traditionally, pressure control was achieved via bypasses and control valves, rarely using inverters. However, due to the general scarcity of water resources in China, applying inverters can save approximately 10% in water and 30% in energy, inevitably reducing the daily operating costs of paper mills.

There are typically two modes for using inverters in water systems: Single Inverter Control and Inverter Alternation Mode.
Single Inverter Control: The inverter's output permanently controls one pump, while the other pumps are powered directly from the line-frequency grid. Their start/stop signals are controlled manually or by PLC logic.
Inverter Alternation Mode: The inverter drives each pump in turn according to a set sequence. The inverter can automatically determine the number of pumps running (within a set range) based on pressure closed-loop control requirements. Only one pump is driven by the inverter at any given time. When the inverter-driven pump reaches the set upper frequency limit and an additional pump is needed, the inverter switches that pump to line-frequency operation and simultaneously starts driving another pump with variable frequency.

IX. Conclusion
In summary, retrofitting paper machinery with inverter drive systems not only demonstrates significant power-saving effects and reduces equipment maintenance costs but also creates substantial economic benefits for enterprises. It can be confidently stated that the application prospects of variable frequency speed control systems in the paper machinery industry will become increasingly broad.